Title: “Qualitative Air Flow Modelling And Analysis Of Data Centre Air Conditioning As Multiple Jet Array
Authors: Premnath, R
Dr.Madhu, G
Keywords: Data Centre air Conditioning
Single Jet
Twin Jet
Triple Jet
Tile Calculations
Issue Date: Nov-2011
Publisher: Cochin University Of Science And Technology
Abstract: In the present study the effect of hot air recirculation is studied with suitable assumptions. It identifies that, the pressure drop across the tile is a dominant parameter which governs the recirculation. The rack suction pressure of the hardware along with the pressure drop across the tile determines the point of recirculation in the cold aisle. The positioning of hardware in the racks play an important role in controlling the recirculation point. The present study is thus helpful in the design of data centre air flow, based on the theory of jets. The air flow can be modelled both quantitatively and qualitatively based on the results
Description: Division Of Safety And Fire Engineering School Of Engineering Cochin University Of Science And Technology